2 Electrical Installation

MICROMASTER 440
Operating Instructions (Compact)

9

Input voltage range

3 AC 380 V – 480 V. ± 10 %

(with built in Class A Filter)

Order No.

6SE6440-

2AD22-

2BA1

2AD23-

0BA1

2AD24-

0BA1

2AD25-

5CA1

2AD27-

5CA1

2AD31-

1CA1

2AD31-

5DA1

Frame Size

B C

D

[kW]

2,2 3,0 4,0 5,5

7,5 11,0 15,0

Output Rating(CT)

[hp]

3,0 4,0 5,0 7,5 10,0 15,0 20,0

Output Power

[kVA]

4,5 5,9 7,8 10,1 14,0 19,8 24,4

CT-Input Current 1)

[A]

7,5 10,0 12,8 15,6 22,0 23,1 33,8

CT-Output Current

[A]

5,9 7,7 10,2 13,2 18,4 26,0 32,0

VT-Input Current 1)

[A]

– – –

17,3

23,1

33,8

37,0

VT-Output Current

[A]

– – –

20,2

29,0

39,0

45,2

Fuse [A]

16 16 20 20 32 35 50

Recommended 3NA

3805 3805 3807 3807 3812 3814 3820

For UL specified

3NE

* * * * * *

1817-0

[mm

2

]

1,5 1,5 2,5 2,5 4,0 6,0 10,0

Input Cable, min.

[AWG]

16 16 14 14 12 10 8

[mm

2

]

6,0 6,0 6,0 10,0 10,0 10,0 35,0

Input Cable, max.

[AWG]

10 10 10 8 8 8 2

[mm

2

]

1,0 1,0 1,0 2,5 4,0 6,0 10,0

Output Cable, min.

[AWG]

18 18 18 14 12 10 8

[mm

2

]

6,0 6,0 6,0 10,0 10,0 10,0 35,0

Output Cable, max.

[AWG]

10 10 10 8 8 8 2

[kg]

3,4 3,4 3,4 5,7 5,7 5,7 17,0

Weight

[lbs]

7,5 7,5 7,5 12,5 12,5 12,5 37,0

[Nm]

1,1 1,5

2,25

Tightening torques for
power terminals

[lbf.in]

(10) (13,3)

(20)

Order No.

6SE6440-

2AD31-

8DA1

2AD32-

2DA1

2AD33-

0EA1

2AD33-

7EA1

2AD34-

5FA1

2AD35-

5FA1

2AD37-

5FA1

Frame Size

D E

F

[kW]

18,5 22,0 30,0 37,0 45,0 55,0 75,0

Output Rating(CT)

[hp]

25,0 30,0 40,0 50,0 60,0 75,0 100,0

Output Power

[kVA]

29,0 34,3 47,3 57,2 68,6 83,8 110,5

CT-Input Current 1)

[A]

37,0 43,0 59,0 72,0 87,0 104,0 139,0

CT-Output Current

[A]

38,0 45,0 62,0 75,0 90,0 110,0 145,0

VT-Input Current 1)

[A]

43,0 59,0 72,0 87,0 104,0

139,0 169,0

VT-Output Current

[A]

45,0 62,0 75,0 90,0 110,0

145,0 178,0

Fuse [A]

63 80 100 125 160 200 250

Recommended 3NA

3822 3824 3830 3832 3836 3140 3144

For UL specified

3NE

1818-0 1820-0 1021-0 1022-0 1224-0 1225-0 1227-0

[mm

2

]

10,0 16,0 25,0 25,0 35,0 70,0 95,0

Input Cable, min.

[AWG]

8 6 3 3 2 2/0

3/0

[mm

2

]

35,0 35,0 35,0 35,0 150,0

150,0 150,0

Input Cable, max.

[AWG]

2 2 2 2

300

300

300

[mm

2

]

10,0 16,0 25,0 25,0 50,0 70,0 95,0

Output Cable, min.

[AWG]

8 6 3 3 1/0

2/0

3/0

[mm

2

]

35,0 35,0 35,0 35,0 150,0

150,0 150,0

Output Cable, max.

[AWG]

2 2 2 2

300

300

300

[kg]

17,0 17,0 22,0 22,0 75,0 75,0 75,0

Weight

[lbs]

37,0 37,0 48,0 48,0 165,0

165,0 165,0

[Nm]

10 50

Tightening torques for
power terminals

[lbf.in]

(89) (445)

1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line

supply V

k

= 2 % referred to the rated drive converter power and a rated line supply voltage

of 400 V without line commutating reactor.

* UL listed fuses such as Class NON from Bussmann are required for use in America