2 Electrical Installation

Issue 10/06

MICROMASTER 440

10

Operating Instructions (Compact)

Input voltage range

3 AC 380 V – 480 V. ± 10 %

(Unfiltered)

Order No.

6SE6440- 2UD13

-7AA1

2UD15

-5AA1

2UD17

-5AA1

2UD21

-1AA1

2UD21

-5AA1

2UD22

-2BA1

2UD23

-0BA1

2UD24

-0BA1

2UD25

-5CA1

2UD27

-5CA1

Frame Size

A B

C

[kW]

0,37 0,55 0,75 1,1

1,5 2,2 3,0 4,0 5,5 7,5

Output Rating(CT)

[hp]

0,5 0,75 1,0 1,5 2,0 3,0 4,0 5,0 7,5 10,0

Output Power

[kVA]

0,9 1,2 1,6 2,3 3,0 4,5 5,9 7,8 10,1 14,0

CT-Input Current 1)

[A]

2,2 2,8 3,7 4,9 5,9 7,5 10,0 12,8 15,6 22,0

CT-Output Current

[A]

1,3 1,7 2,2 3,1 4,1 5,9 7,7 10,2 13,2 19,0

VT-Input Current 1)

[A]

- - - - - - - -

17,3

23,1

VT-Output Current

[A]

- - - - - - - -

19,0

26,0

Fuse [A]

10 10 10 10 10 16 16 20 20 32

Recommended 3NA

3803 3803 3803 3803 3803 3805 3805 3807 3807 3812

For UL specified

*

*

*

*

*

*

*

*

*

*

[mm

2

]

1,0 1,0 1,0 1,0 1,0 1,5 1,5 2,5 2,5 4,0

Input Cable, min.

[AWG]

18 18 18 18 18 16 16 14 14 12

[mm

2

]

2,5 2,5 2,5 2,5 2,5 6,0 6,0 6,0 10,0 10,0

Input Cable, max.

[AWG]

14 14 14 14 14 10 10 10 8 8

[mm

2

]

1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0 2,5 4,0

Output Cable, min.

[AWG]

18 18 18 18 18 18 18 18 14 12

[mm

2

]

2,5 2,5 2,5 2,5 2,5 6,0 6,0 6,0 10,0 10,0

Output Cable, max.

[AWG]

14 14 14 14 14 10 10 10 8 8

[kg]

1,3 1,3 1,3 1,3 1,3 3,3 3,3 3,3 5,5 5,5

Weight

[lbs]

2,9 2,9 2,9 2,9 2,9 7,3 7,3 7,3 12,1 12,1

[Nm]

1,1 1,5

2,25

Tightening torques for
power terminals

[lbf.in]

(10) (13,3)

(20)

Order No.

6SE6440- 2UD31

-1CA1

2UD31

-5DA1

2UD31

-8DA1

2UD32

-2DA1

2UD33

-0EA1

2UD33

-7EA1

2UD34

-5FA1

2UD35

-5FA1

2UD37

-5FA1

Frame Size

C D

E

F

[kW]

11,0 15,0 18,5 22,0 30,0 37,0 45,0 55,0 75,0

Output Rating(CT)

[hp]

15,0 20,0 25,0 30,0 40,0 50,0 60,0 75,0 100,0

Output Power

[kVA]

19,8 24,4 29,0 34,3 47,3 57,2 68,6 83,8 110,5

CT-Input Current 1)

[A]

23,1 33,8 37,0 43,0 59,0 72,0 87,0 104,0 139,0

CT-Output Current

[A]

26,0 32,0 38,0 45,0 62,0 75,0 90,0 110,0 145,0

VT-Input Current 1)

[A]

33,8 37,0 43,0 59,0 72,0 87,0 104,0 139,0 169,0

VT-Output Current

[A]

32,0 38,0 45,0 62,0 75,0 90,0 110,0 145,0 178,0

Fuse [A]

35 50 63 80 100 125 160 200 250

Recommended 3NA

3814 3820 3822 3824 3830 3832 3836 3140 3144

For UL specified

3NE

* 1817-0 1818-0 1820-0 1021-0 1022-0 1224-0

1225-0

1227-0

[mm

2

]

6,0 10,0 10,0 16,0 25,0 25,0 35,0 70,0 95,0

Input Cable, min.

[AWG]

10 8 8 6 3 3 2 2/0

3/0

[mm

2

]

10,0 35,0 35,0 35,0 35,0 35,0 150,0 150,0 150,0

Input Cable, max.

[AWG]

8 2 2 2 2 2 300

300

300

[mm

2

]

6,0 10,0 10,0 16,0 25,0 25,0 35,0 70,0 95,0

Output Cable, min.

[AWG]

10 8 8 6 3 3 2 2/0

3/0

[mm

2

]

10,0 35,0 35,0 35,0 35,0 35,0 150,0 150,0 150,0

Output Cable, max.

[AWG]

8 2 2 2 2 2 300

300

300

[kg]

5,5 16,0 16,0 16,0 20,0 20,0 56,0 56,0 56,0

Weight

[lbs]

12,1 35,0 35,0 35,0 44,0 44,0 123,0 123,0 123,0

[Nm]

2,25 10

50

Tightening torques for
power terminals

[lbf.in]

(20) (89)

(445)

1) Secondary conditions:

Input current at the rated operating point - applies for the short-circuit voltage of the line
supply V

k

= 2 % referred to the rated drive converter power and a rated line supply voltage

of 400 V without line commutating reactor.

* UL listed fuses such as Class NON from Bussmann are required for use in America