beautypg.com

4 digital outputs (dout) – Siemens MICROMASTER 440 User Manual

Page 36

background image

6 Commissioning

Issue 10/06

MICROMASTER 440

36

Operating Instructions (Compact)

6.4.4

Digital outputs (DOUT)

BI: Function of digital output 1 *
Defines source of digital output 1.

BI: Function of digital output 2 *
Defines source of digital output 2.

BI: Function of digital output 3 *
Defines source of digital output 3.

CO/BO: State of digital outputs
Displays status of digital outputs (also
includes inversion of digital outputs via
P0748).

Invert digital output
Defines high and low states of relay for a
given function.

Common Settings:

Closed

52.0 Drive

ready

0

52.1

Drive ready to run

0

52.2 Drive

running

0

52.3 Drive fault active

0

52.4 OFF2

active

1

52.5 OFF3

active

1

52.6 Switch on inhibit active

0

52.7 Drive

warning

active

0

52.8 Deviation setpoint/actual value

1

52.9 PZD control (Process Data Control) 0
52.A Maximum frequency reached

0

52.B Warning: Motor current limit

1

52.C Motor holding brake (MHB) active

0

52.D Motor

overload

1

52.E Motor running direction right

0

52.F Inverter

overload

1

53.0 DC brake active

0

53.1 Act. freq. f_act > P2167 (f_off)

0

53.2 Act. freq. f_act <= P1080 (f_min)

0

53.3 Act. current r0027 > P2170

0

53.4 Act. freq. f_act > P2155 (f_1)

0

53.5 Act. freq. f_act <= P2155 (f_1)

0

53.6 Act. freq. f_act >= setpoint

0

53.7 Act. Vdc r0026 < P2172

0

53.8 Act. Vdc r0026 > P2172

0

53.A PID output

r2294 == P2292 (PID_min)

0

53.B PID output

r2294 == P2291 (PID_max)

0

(52:3)

BI: Fct. of DOUT 1

P0731.C

-1

0

1

Invert DOUTs

0 ... 7

P0748 (0)

CO/BO: State DOUTs

r0747

r0747

Kl.20

Kl.18

.0

Function

xxxx.y

rxxxx.y

P0731 = xxxx.y

DOUT channel

Relay :

DC 30 V / 5 A
AC 250 V / 2 A

Kl.28

Kl.9

int. 24 V
max. 100 mA

NO

COM

NC

Kl.19

or

Text

max. opening / closing time

5 / 10 ms

52.3

0

P0731 = ...

52.7

0.0

P0748 = ...

P0733 = ...

P0732 = ...

r0747 = ...