2 Electrical Installation

Issue 10/06

MICROMASTER 440

6

Operating Instructions (Compact)

2 Electrical

Installation

2.1 Technical

Specifications

Input voltage range

1 AC 200 V – 240 V, ± 10 %

(Unfiltered and with built in Class A Filter)

2AB

Order No
6SE6440-

2UC

11-

2AA1

12-

5AA1

13-

7AA1

15-

5AA1

17-

5AA1

21-

1BA1

21-

5BA1

22-

2BA1

23-

0CA1

Frame Size

A B

C

[kW]

0,12 0,25 0,37 0,55

0,75 1,1 1,5 2,2 3,0

Output Rating (CT)

[hp]

0,16 0,33 0,5 0,75 1,0 1,5 2,0 3,0 4,0

Output Power

[kVA]

0,4 0,7 1,0 1,3 1,7 2,4 3,2 4,6 6,0

CT Input Current 1)

1,8 3,2 4,6 6,2 8,2 11,0 14,4 20,2 35,5

CT Output Current

[A]

0,9 1,7 2,3 3,0 3,9 5,5 7,4 10,4 13,6

Fuse

10 10 10 16 16 20 20 32 40

Recommended

3NA

3803 3803 3803 3805 3805 3807 3807 3812 3817

for UL specified

* * * * * * * * *

[mm

2

]

1,0 1,0 1,0 1,5 1,5 2,5 2,5 4,0 6,0

Input Cable Min.

[AWG]

18 18 18 16 16 14 14 12 10

[mm

2

]

2,5 2,5 2,5 2,5 2,5 6,0 6,0 6,0 10,0

Input Cable Max.

[AWG]

14 14 14 14 14 10 10 10 8

[mm

2

]

1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,5

Output Cable Min.

[AWG]

18 18 18 18 18 18 18 18 16

[mm

2

]

2,5 2,5 2,5 2,5 2,5 6,0 6,0 6,0 10,0

Output Cable Max.

[AWG]

14 14 14 14 14 10 10 10 8

[kg]

1,3 1,3 1,3 1,3 1,3 3,4 3,4 3,4 5,7

Weight
(with built in filter)

[lbs]

2,9 2,9 2,9 2,9 2,9 7,5 7,5 7,5 12,5

[kg]

1,3 1,3 1,3 1,3 1,3 3,3 3,3 3,3 5,5

Weight (unfiltered)

[lbs]

2,9 2,9 2,9 2,9 2,9 7,3 7,3 7,3 12,1

[Nm]

1,1 1,5

2,25

Tightening torques for
power terminals

[lbf.in]

(10) (13,3)

(20)

1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line

supply V

k

= 2 % referred to the rated drive converter power and a rated line supply voltage

of 240 V without line commutating reactor.

* UL listed fuses such as Class NON from Bussmann are required for use in America