Issue 10/06

6 Commissioning

MICROMASTER 440
Operating Instructions (Compact)

75

6.5 Series

commissioning

An existing parameter set can be transferred to a MICROMASTER 440 frequency
inverter using STARTER or DriveMonitor (refer to Section 4.1 "Establishing
communications MICROMASTER 440

⇔ STARTER").

Typical applications for series commissioning include:

1. If several drives are to be commissioned that have the same configuration and

same functions. A quick / application commissioning (first commissioning) must
be carried-out for the first drive. Its parameter values are then transferred to the
other drives.

2. When replacing MICROMASTER 440 frequency inverters.

6.6

Parameter reset of factory setting


User access level
1 Standard

Parameter filter
0 All parameters

Commissioning parameter
30 Factory

setting

Factory reset
0 disabled
1 Parameter reset

The drive inverter carries-out a parameter reset (duration, approx. 10 s) and then
automatically exits the reset menu and sets:

P0970 = 0 :

disabled

P0010 = 0 :

ready



START

END

P0010 = 30

P0970 = 1

0

0

P0003 = 1

P0004 = 0

1

0