beautypg.com

2 motor data identification, 3 magnetizing current – Siemens MICROMASTER 440 User Manual

Page 32

background image

6 Commissioning

Issue 10/06

MICROMASTER 440

32

Operating Instructions (Compact)

6.2

Motor data identification

Factory setting

Ambient motor temperature

(entered in °C)

The motor ambient temperature is entered at the instant that motor data is
being determined (factory setting: 20 °C).




yes no

The difference between the motor temperature and the motor ambient
temperature P0625 must lie in the tolerance range of approx. ± 5 °C. If this is
not the case, then the motor data identification routine can only be carried-out
after the motor has cooled down.


Select motor data identification

with P1910 = 1

p1910 = 1: Identifies the motor parameter with parameter change.

These are accepted and applied to the controller.

When p1910 = 1 is selected, Alarm A0541 (motor data identification active)
is output, and internally p0340 is set to 3.

Starts the motor data identification run

with p1910 = 1

The measuring operation is initiated with the continuous (steady-state) ON
command. The motor aligns itself and current flows through it. Diagnostics is
possible using r0069 (CO: Phase current).

After the motor data identification routine has been completed, p1910 is reset
(p1910 = 0, motor data identification routine inhibited) and Alarm A0541 is
cleared (deleted).

In order to set the frequency converter into a defined state, an OFF1 command
must be issued before the next step.

Select motor data identification

with P1910 = 3

p1910 = 3: Identifies the saturation characteristic with parameter change.
When p1910 = 3 is selected, Alarm A0541 (motor data identification active)
is output and internally, p0340 is set to 2.

Starts the motor data identification run

with P1910 = 3

The measuring operation must be started with a continuous ON command.

After the motor identification routine has been completed, p1910 is reset
(p1910 = 0, motor data identification routine inhibited) and Alarm A0541 is
cleared (deleted).

In order to set the frequency converter into a defined state, an OFF1 command
must be issued before the next step.

6.3 Magnetizing

current

¾

The value of the magnetizing current r0331/P0320 has a significant influence on

the closed-loop control. This cannot be measured at standstill. This means that
the value is estimated for standard 4-pole 1LA7 Siemens standard using the
automatic parameterization P0340=1 (P0320=0; result in r0331).

¾

If the deviation of the magnetizing current is too high, then the values for the

magnetizing reactance and those of the rotor resistance will not be able to be
accurately determined.

¾

Especially for third-party motors it is important that the magnetizing current

that is determined, is carefully checked and if required, appropriately corrected.

START

P0625 = ?

20 °C

| Motor temp. - P0625|

≤ 5 °C ?

Allow the motor

to cool down

P1910 = 1

0

A0541

ON

OFF1

P1910 = 3

0

A0541

ON

OFF1

END