6 Commissioning

Issue 10/06

MICROMASTER 440

52

Operating Instructions (Compact)

Control word of motor model

This parameter controls the operation of the sensorless vector control (SLVC) at very low
frequencies.

This therefore includes the following conditions:

Bit00 Start SLVC open loop 0 NO 1 YES

(Operation directly after an ON command)
Bit01 Zero crossing SLVC open loop 0 NO 1 YES

(zero crossing)

f

t

p1755

Closed loop

Open loop

Start

f

t

Closed loop

Open loop

Zero crossing

p1755

p1755

For most applications the setting of parameter p1750 = 0 gives the best result at low
frequency.

Start-freq. motor model (SLVC)
Enter the start frequency of sensorless vector control (SLVC), thereby SLVC switches over
from open-loop to closed-loop at that frequency.

.

.

r0062

Speed

controller

Pre-

control

Torque

limitation

Current

controller

i

sq

open/closed

loop

Flux setpoint

closed loop

Flux setpoint

open loop

i

sd

p1610

p1611

+

+

0

Act. output

voltage

Act. output

frequency

Act. frequency

Current

measurement

Act. angle

Observer model

closed loop

Slip

Frequency

setpoint

i

u

i

w

i

v

p1452

p1470 p1472

p1750/p1755

P1750 = ...

P1755 = ...

1

5.0 Hz