Siemens MICROMASTER 440 User Manual
Page 57
Issue 10/06
6 Commissioning
MICROMASTER 440
Operating Instructions (Compact)
57
BI: Fct digital output 1
Defines the source for digital output 1.
NOTE
The brake relay can also be controlled
from another digital output (if this is
available) or using a distributed I/O
module. Analog to DOUT 1, it should
be guaranteed that the I/Os are
controlled by the status bit “MHB
active”.
Inverting digital
outputs
This parameter allows the signals
to be output to be inverted.
Frequent settings:
52.0 Ready to power-up
0 Closed
52.1 Ready
0 Closed
52.2 Drive operational
0 Closed
52.3 Fault present
0 Closed
52.4 OFF2 active (present)
1 Closed
52.5 OFF3 active (present)
1 Closed
52.6 Power-on inhibit active (present)
0 Closed
52.7 Alarm active (present) 0
Closed
52.8 Deviation,
setpoint/actual value
1 Closed
52.9 PZD / PLC control
0 Closed
52.A Maximum frequency reached
0 Closed
52.B Alarm: Motor current limit
1 Closed
52.C Motor holding brake active
0 Closed
52.D Motor overload
1 Closed
52.E Motor dir. of rotation, clockwise
0 Closed
52.F Frequency inverter overload
1 Closed
53.0 DC brake active
0 Closed
53.1 Actual freq. f_act > P2167 (f_off) 0 Closed
:
:
(52:3)
BI: Fct. of DOUT 1
P0731.C
-1
0
1
Invert DOUTs
0 ... 7
P0748 (0)
CO/BO: State DOUTs
r0747
r0747
Kl.20
Kl.18
.0
Function
xxxx.y
rxxxx.y
P0731 = xxxx.y
DOUT channel
Relay :
DC 30 V / 5 A
AC 250 V / 2 A
Kl.28
Kl.9
int. 24 V
max. 100 mA
NO
COM
NC
Kl.19
or
Text
- max. opening / closing time
5 / 10 ms
Holding brake release delay
(entered in s)
Defines the time interval during which the frequency inverter runs with the min. frequency
p1080 after magnetizing, before the ramp-up starts.
P1216
≥ brake opening time + relay opening time
Holding time after ramp-down
(entered in s)
Defines time for which inverter runs at minimum frequency (p1080) after ramping down.
P1217
≥ brake closing time + relay closing time
P1217 = ...
1.0 s
P1216 = ...
1.0 s
0
52.3
P0731=52.C
P0748 = 0