6 Commissioning
MICROMASTER 440
Operating Instructions (Compact)
73
r0054 CO/BO: Control word 1
Displays the first control word (STW) of the frequency inverter and can be used to display
the active commands.
Bit00 ON/OFF1 0 NO 1 YES
Bit01 OFF2: Electrical stop 0 YES 1 NO
Bit02 OFF3: Fast stop 0 YES 1 NO
Bit03 Pulse enable 0 NO 1 YES
Bit04 RFG enable 0 NO 1 YES
Bit05 RFG start 0 NO 1 YES
Bit06 Setpoint enable 0 NO 1 YES
Bit07 Fault acknowledge 0 NO 1 YES
Bit08 JOG right 0 NO 1 YES
Bit09 JOG left 0 NO 1 YES
Bit10 Control from PLC 0 NO 1 YES
Bit11 Reverse (setpoint inversion) 0 NO 1 YES
Bit13 Motor potentiometer MOP up 0 NO 1 YES
Bit14 Motor potentiometer MOP down 0 NO 1 YES
Bit15 CDS Bit 0 (Local/Remote) 0 NO 1 YES
r0063 CO: Actual frequency
Displays the actual frequency in Hz.
V/f
0
1,2
SLVC
(observer
model)
Encoder
P0400
P1300
160 ms
Frequency actual values:
Smoothed freq. actual value
Frequency actual value
Freq.act.value fr. the encoder
21,23
20,22
<20
0
P1300 = 21,23 and P0400 = 0 --> F0090
P0408
60
r0313
⋅
Smoothed speed act. value
r0313
60
r0022
r0021
r0063
r0061
r0067 CO: Act. output current limit
Displays valid maximum output current of inverter.
Motor
Inverter
Motor protection
P0640
r0067
P0305
Inverter protection
r0209
Min
r0072 CO: Act. output voltage
Displays output voltage.