20 diagnostic parameters – Siemens MICROMASTER 440 User Manual
Page 72
6 Commissioning
Issue 10/06
MICROMASTER 440
72
Operating Instructions (Compact)
6.4.20 Diagnostic
parameters
r0021 CO: Act. filtered frequency
Displays actual inverter output frequency (r0021) excluding slip compensation, resonance
damping and frequency limitation.
r0022 Act. filtered rotor speed
Displays calculated rotor speed based on inverter output frequency [Hz] x 120 / number of
poles.
r0313
60
[Hz]
r0021
[1/min]
r0022
⋅
=
r0032 CO: Act. filtered power
Displays motor power (power output at the motor shaft).
Motor
ω, M
M
f
2
M
P
mech
⋅
⋅
π
⋅
=
⋅
ω
=
⇒
[Nm]
r0031
[1/min]
60
r0022
π
2
1000
1
[kW]
r0032
⋅
⋅
⋅
⋅
=
[kW]
r0032
0.75
[hp]
r0032
⋅
=
r0035 CO: Motor temperature
Displays the measured motor temperature in °C.
r0036 CO: Frequency inverter utilization
Displays the frequency inverter utilization as a % referred to the overload. In so doing, the
value is calculated using the I
2
t model.
The I
2
t actual value relative to the maximum possible I
2
t value provides the level of
utilization.
r0039 CO: Energy consumpt. meter [kWh]
Displays electrical energy used by inverter since display was last reset.
ist
dt
cos
i
u
3
dt
P
r0039
0
0
W
⋅
ϕ
⋅
⋅
⋅
∫
=
⋅
∫
=
ist
t
t
r0052 CO/BO: Act. status word 1
Displays the first active status word (ZSW) of the frequency inverter (bit format) and can be
used to diagnose the inverter status.
Bit00 Drive ready 0 NO 1 YES
Bit01 Drive ready to run 0 NO 1 YES
Bit02 Drive running 0 NO 1 YES
Bit03 Drive fault active 0 NO 1 YES
Bit04 OFF2 active 0 YES 1 NO
Bit05 OFF3 active 0 YES 1 NO
Bit06 ON inhibit active 0 NO 1 YES
Bit07 Drive warning active 0 NO 1 YES
Bit08 Deviation setpoint / act. value 0 YES 1 NO
Bit09 PZD control 0 NO 1 YES
Bit10 Maximum frequency reached 0 NO 1 YES
Bit11 Warning: Motor current limit 0 YES 1 NO
Bit12 Motor holding brake active 0 NO 1 YES
Bit13 Motor overload 0 YES 1 NO
Bit14 Motor runs right 0 NO 1 YES
Bit15 Inverter overload 0 YES 1 NO