beautypg.com

6 dynamic braking, 7 vdc controller – Siemens MICROMASTER 440 User Manual

Page 60

background image

6 Commissioning

Issue 10/06

MICROMASTER 440

60

Operating Instructions (Compact)

6.4.18.6 Dynamic

braking

The following settings should always be made:
¾

The Vdc_max controller de-activated

P1240 = 0

(def.: P1240 = 1)

¾

The compound brake de-activated

P1236 = 0

(def.: P1236 = 0)

¾

Resistor brake activated

P1237 > 0

(def.: P1237 = 0)

Dynamic braking
Dynamic braking is activated using parameter P1237 – the nominal (rated) duty cycle as
well as the switch-in duration of the braking resistor are also defined.
0 Inhibited
1 Load duty cycle 5 %
2 Load duty cycle 10 %
3 Load duty cycle 20 %
4 Load duty cycle 50 %
5 Load duty cycle 100 %
Using the dynamic brake, the regenerative feedback energy is transferred to the external
braking resistor using the chopper control (braking chopper); it is converted into thermal
energy (heat) in this resistor. This dynamic braking allows the drive to be braked in a
controlled fashion. This function is not available for sizes FX and GX.

Chopper resistor

Chopper

control

B-

=

~

~

B+

=

~

MM4

6.4.18.7 Vdc

controller

Configuration of Vdc controller
Enables / disables Vdc controller.
0 Vdc controller disabled
1 Vdc-max controller enabled

P1254 =...

Auto detect Vdc switch-on levels
Enables/disables auto-detection of switch-on
levels for Vdc control functionalities.
0 Disabled
1 Enabled

t

t

⏐f⏐

1

-controller active

V

DC_max

t

V

DC

0

r0056 Bit14

r1242

A0911

f

f

act

set

P1237 = ...

0

1

1

P1240 =...