Siemens MICROMASTER 440 User Manual
Page 8
2 Electrical Installation
Issue 10/06
MICROMASTER 440
8
Operating Instructions (Compact)
Input voltage range
3 AC 200 V – 240 V. ± 10 %
(Unfiltered)
Order No.
6SE6440- 2UC11
-2AA1
2UC12
-5AA1
2UC13
-7AA1
2UC15
-5AA1
2UC17
-5AA1
2UC21
-1BA1
2UC21
-5BA1
2UC22
-2BA1
2UC23
-0CA1
Frame Size
A B C
[kW]
0,12 0,25 0,37 0,55
0,75 1,1 1,5 2,2 3,0
Output Rating(CT)
[hp]
0,16 0,33 0,5 0,75 1,0 1,5 2,0 3,0 4,0
Output Power
[kVA]
0,4 0,7 1,0 1,3 1,7 2,4 3,2 4,6 6,0
CT-Input Current 1)
[A]
1,1 1,9 2,7 3,6 4,7 6,4 8,3 11,7 15,6
CT-Output Current
[A]
0,9 1,7 2,3 3,0 3,9 5,5 7,4 10,4 13,6
Fuse [A]
10 10 10 16 16 20 20 25 25
Recommended 3NA
3803 3803 3803 3805 3805 3807 3807 3810 3810
For UL specified
* * * * * * * * *
[mm
2
]
1,0 1,0 1,0 1,5 1,5 2,5 2,5 2,5 4,0
Input Cable, min.
[AWG]
18 18 18 16 16 14 14 14 12
[mm
2
]
2,5 2,5 2,5 2,5 2,5 6,0 6,0 6,0 10,0
Input Cable, max.
[AWG]
14 14 14 14 14 10 10 10 8
[mm
2
]
1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,5
Output Cable, min.
[AWG]
18 18 18 18 18 18 18 18 16
[mm
2
]
2,5 2,5 2,5 2,5 2,5 6,0 6,0 6,0 10,0
Output Cable, max.
[AWG]
14 14 14 14 14 10 10 10 8
[kg]
1,3 1,3 1,3 1,3 1,3 3,3 3,3 3,3 5,5
Weight
[lbs]
2,9 2,9 2,9 2,9 2,9 7,3 7,3 7,3 12,1
[Nm]
1,1 1,5 2,25
Tightening torques
for power terminals
[lbf.in]
(10) (13,3) (20)
Order No.
6SE6440- 2UC24-
0CA1
2UC25-
5CA1
2UC27-
5DA1
2UC31-
1DA1
2UC31-
5DA1
2UC31-
8EA1
2UC32-
2EA1
2UC33-
0FA1
2UC33-
7FA1
2UC34-
5FA1
Frame Size
C D E F
[kW]
4,0 5,5 7,5 11,0
15,0 18,5 22,0 30,0 37,0 45,0
Output Rating(CT)
[hp]
5,0 7,5 10,0 15,0 20,0 25,0 30,0 40,0 50,0 60,0
Output Power
[kVA]
7,7 9,6 12,3 18,4 23,7 29,8 35,1 45,6 57,0 67,5
CT-Input Current 1)
[A]
19,7 26,5 34,2 38,0 50,0 62,0 71,0 96,0 114,0 135,0
CT-Output Current
[A]
17,5 22,0 28,0 42,0 54,0 68,0 80,0 104,0
130,0 154,0
VT-Input Current 1)
[A]
28,3 34,2 38,0 50,0 62,0 71,0 96,0 114,0
135,0 164,0
VT-Output Current
[A]
22,0 28,0 42,0 54,0 68,0 80,0 104,0
130,0
154,0 -
Fuse
[A]
32 35 50 80 80 100 125
200
200 250
Recommended 3NA
3812 3814 3820 3824 3824 3830 3832 3140 3142 3144
For UL specified
3NE
* *
1817-0 1820-0 1820-0 1021-0 1022-0
1225-0
1225-0
1227-0
[mm
2
]
4,0 4,0 10,0 16,0 16,0 25,0 25,0 70,0 70,0 95,0
Input Cable, min.
[AWG]
12 12 8 6 6 3 3 2/0
2/0
3/0
[mm
2
]
10,0 10,0 35,0 35,0 35,0 35,0 35,0 150,0
150,0 150,0
Input Cable, max.
[AWG]
8 8 2 2 2 2 2
300
300
300
[mm
2
]
4,0 4,0 10,0 16,0 16,0 25,0 25,0 50,0 70,0 95,0
Output Cable, min.
[AWG]
12 12 8 6 6 3 3 1/0
2/0
3/0
[mm
2
]
10,0 10,0 35,0 35,0 35,0 35,0 35,0 150,0
150,0 150,0
Output Cable, max
[AWG]
8 8 2 2 2 2 2
300
300
300
[kg]
5,5 5,5 17,0 16,0 16,0 20,0 20,0 55,0 55,0 55,0
Weight
[lbs]
12,1 12,1 37,0 35,0 35,0 44,0 44,0 121,0
121,0 121,0
[Nm]
2,25 10
50
Tightening torques
for power terminals
[lbf.in]
(20) (89)
(445)
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line
supply V
k
= 2 % referred to the rated drive converter power and a rated line supply voltage
of 240 V without line commutating reactor.
* UL listed fuses such as Class NON from Bussmann are required for use in America