6 Commissioning

Issue 10/06

MICROMASTER 440

56

Operating Instructions (Compact)

6.4.18.3 Holding

brake

¾

Series / commissioning for hazardous loads
− lower the load to the floor

− when replacing the frequency inverter, prevent (inhibit) the frequency

inverter from controlling the motor holding brake (MHB)

− secure the load or inhibit the motor holding brake control (so that the brake

cannot be controlled) and then – and only then – carry-out quick
commissioning / parameter download using the PC-based tool (e.g.
STARTER, AOP)

¾

Parameterize the weight equalization for hoisting gear applications
− magnetizing time P0346 greater than zero

− min. frequency P1080 should approximately correspond to the motor slip

r0330 (P1080 ≈ r0330)

− adapt the voltage boost to the load

a) V/f (P1300 = 0 ...3): P1310, P1311
b) SLVC (P1300 =20): P1610, P1611

¾

It is not sufficient to just select the status signal r0052 bit 12 "motor holding

brake active" in P0731 – P0733. In order to activate the motor holding brake, in
addition, parameter P1215 must be set to 1.

¾

It is not permissible to use the motor holding brake as operating brake. The

reason for this is that the brake is generally only dimensioned/designed for a
limited number of emergency braking operations.

¾

The brake closing / opening times can be taken from the appropriate manual.

The following typical values have been taken from Motor Catalog M11
2003/2004, Page 2/51:

Motor size

Brake type

Opening time [ms]

Closing time [ms]

63 2LM8

005-1NAxx 25

56

71 2LM8

005-2NAxx 25

56

80 2LM8

010-3NAxx 26

70

90 2LM8

020-4NAxx 37

90

100 2LM8

040-5NAxx 43

140

112 2LM8

060-6NAxx 60

210

132 2LM8

100-7NAxx 50

270

160 2LM8

260-8NAxx 165

340

180 2LM8

315-0NAxx 152

410

200
225

2LM8 400-0NAxx

230

390

Holding brake enable
Enables/disables holding brake function (MHB).
0 Motor holding brake disabled
1 Motor holding brake enabled
NOTE
The following must apply when controlling the brake relay via a digital output: P0731 = 52.C
(= 52.12) (refer to Section 6.4.4 "Digital outputs (DOUT)").

0