2 Electrical Installation

MICROMASTER 440
Operating Instructions (Compact)

7

Input voltage range

3 AC 200 V – 240 V. ± 10 %

(with built in Class A Filter)

Order No.

6SE6440- 2AC23-

0CA1

2AC24-

0CA1

2AC25-

5CA1

Frame Size

C

[kW]

3,0 4,0 5,5

Output Rating(CT)

[hp]

4,0 5,0 7,5

Output Power

[kVA]

6,0 7,7 9,6

CT Input Current 1)

[A]

15,6 19,7 26,5

CT-Output Current

[A]

13,6 17,5 22,0

VT Input Current 1)

[A]

- 28,3

34,2

VT-Output Current

[A]

- 22,0

28,0

Fuse [A]

25 32 35

Recommended 3NA

3810 3812 3814

For UL specified

* * *

[mm

2

]

2,5 4,0 4,0

Input Cable, min.

[AWG]

14 12 12

[mm

2

]

10,0 10,0 10,0

Input Cable, max.

[AWG]

8 8 8

[mm

2

]

1,5 4,0 4,0

Output Cable, min.

[AWG]

16 12 12

[mm

2

]

10,0 10,0 10,0

Output Cable, max.

[AWG]

8 8 8

[kg]

5,7 5,7 5,7

Weight

[lbs]

12,5 12,5 12,5

[Nm]

2,25

Tightening torques for
power terminals

[lbf.in]

(20)

1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line

supply V

k

= 2 % referred to the rated drive converter power and a rated line supply voltage

of 240 V without line commutating reactor.

* UL listed fuses such as Class NON from Bussmann are required for use in America