Issue 10/06
6 Commissioning
MICROMASTER 440
Operating Instructions (Compact)
55
6.4.18 Converter-specific
Functions
6.4.18.1 Flying
start
Flying start
Starts inverter onto a spinning motor by rapidly changing the output frequency of the
inverter until the actual motor speed has been found.
0 Flying start disabled
1 Flying start is always active, start in direction of setpoint
2 Flying start is active if power on, fault, OFF2, start in direction of setpoint
3 Flying start is active if fault, OFF2, start in direction of setpoint
4 Flying start is always active, only in direction of setpoint
5 Flying start is active if power on, fault, OFF2, only in direction of setpoint
6 Flying start is active if fault, OFF2, only in direction of setpoint
Motor-current: Flying start
(entered in %)
Defines search current used for flying start.
Search rate: Flying start
(entered in %)
Sets factor by which the output frequency changes during flying start to synchronize with
turning motor.
6.4.18.2 Automatic
restart
Automatic restart
Configures automatic restart function.
0 Disabled
1 Trip reset after power on
2 Restart after mains blackout
3 Restart after mains brownout or fault
4 Restart after mains brownout
5 Restart after mains blackout and fault
6 Restart after mains brown/blackout or fault
P1210 = ...
1
0
100 %
100 %
P1200 = ...
P1202 = ...
P1203 = ?