beautypg.com

Siemens MICROMASTER 440 User Manual

Page 30

background image

6 Commissioning

Issue 10/06

MICROMASTER 440

30

Operating Instructions (Compact)

BOP

USS

BOP link

USS

COM link

P0700 = 2

Terminals

CB

COM link

Sequence control

Setpoint

channel

Motor

control

P1000 =...

Selection of frequency setpoint *
(enters the frequency setpoint source)
1 MOP setpoint
2 Analog setpoint
3 Fixed frequency
4 USS on BOP link
5 USS on COM link (control terminals 29 and 30)
6 CB on COM link (CB = communications module)
7 Analog setpoint 2
10 No main setpoint + MOP setpoint
11 MOP setpoint + MOP setpoint
12 Analog setpoint + MOP setpoint

..

.

76 CB on COM link + Analog setpoint 2
77 Analog setpoint 2 + Analog setpoint 2

P1080 =...

Min. frequency
(enters the minimum motor frequency in Hz)
Sets minimum motor frequency at which motor will run irrespective of frequency
setpoint. The value set here is valid for both clockwise and anticlockwise rotation.

P1082 =...

Max. frequency
(enters the maximum motor frequency in Hz)
Sets maximum motor frequency at which motor will run irrespective of the
frequency setpoint. The value set here is valid for both clockwise and
anticlockwise rotation.

P1120 =...

Ramp-up time

(enters the ramp-up time in s)
Time taken for motor to accelerate from standstill up to maximum motor
frequency (P1082) when no rounding is used. If a ramp-up time is parameterized
which is too low, then this can result in alarm A0501 (current limit value) or the
drive inverter being shutdown with fault F0001 (overcurrent).

P1121 =...

Ramp-down time
(enters the deceleration time in s)
Time taken for motor to decelerate from maximum motor frequency (P1082) down
to standstill when no rounding is used. If the ramp-down time is parameterized too
low, then this can result in alarms A0501 (current limit value), A0502 (overvoltage
limit value) or the drive inverter being powered-down with fault F0001
(overcurrent) or F0002 (overvoltage).

OFF3 ramp-down time

(enters the fast stop ramp-down time in s)
Enters the time, for example, with which the motor should be braked from the
maximum frequency P1082 down to standstill for an OFF3 command (fast stop).
If the ramp-down time is parameterized too low, then this can result in alarms
A0501 (current limit value), A0502 (overvoltage limit value) or the drive inverter
being shutdown with fault F0001 (overcurrent) or F0002 (overvoltage).

2

0.00 Hz

50.00 Hz

10.00 s

10.00 s

5.00 s

P1135 =...