48TPTQ-104S Rev 1 ♦ 47TQuantum Platform
Module Configuration
46TIEC 60870-5-104 Server for Quantum
12TUser Manual
5.11 [M_DP_NA_1 104]
This section defines the monitored dual-point database. This information is
sourced from the database and is transferred to the remote Client unit. Each
point in the database can have one of four possible states, 00 = intermediate, 01
= Point Off, 10 = Point On, and 11 = intermediate).
This section takes the following parameters:
Point #
DB Address
Group(s)
IV DB Bit
Each point is two bits and the DB address value corresponds to the bit offset in
the module memory database. For additional information on how to set these
parameters, see the Reference chapter of this manual.
5.12 [M_ST_NA_1 104]
This section defines the monitored step database. This information is sourced
from the database and is transferred to the remote Client unit.
This section takes the following parameters:
Point #
DB Address
Group(s)
IV DB Bit
Each point is one 8-bit byte and the DB Address value corresponds to the byte
offset in the module memory database. For additional information on how to set
these parameters, see the Reference chapter of this manual.
5.13 [M_BO_NA_1 104]
This section defines the 32-bit Bitstring database for the server device emulated.
This information is sourced from the database and is transferred to the remote
client unit.
This section takes the following parameters:
Point #
DB Address
Group (page 98)
IV DB Bit
Each point is four, 8-bit bytes (two, 16-bit words) and the DB
A
DDRESS
value
corresponds to the double-word offset in the module memory database.
The DB
ADDRESS
should be located in a database area that is being constantly
moved from the Quantum to the Master.
For additional information on how to set these parameters, see the Reference
chapter of this manual.
ProSoft Technology, Inc.
Page 93 of 201
March 4, 2013