9 [iec-870-5-104 ip addresses, 10 [m_sp_na_1 104, Iec-870-5-104 ip addresses – ProSoft Technology PTQ-104S User Manual
Page 92: M_sp_na_1 104

Module Configuration
48TPTQ-104S Rev 1 ♦ 47TQuantum Platform
12TUser Manual
46TIEC 60870-5-104 Server for Quantum
Note: The Low Limit and High Limit threshold values are always calculated based on the threshold
deadband value as described in the following table.
Point
Value
Threshold
Determined by the deadband set in the configuration file or altered by the write
command.
Low Limit
Last reported event value - threshold.
High Limit
Last reported event value + threshold.
5.9
[IEC-870-5-104 IP Addresses]
This section enters the IP addresses for the hosts to connect to this unit. The unit
will only accept connections from hosts listed here. This list may contain up to 10
entries between the START and END labels. The address must start in column 1,
and must be entered in standard dot notation.
The following is an example of the [IEC-870-5-104 IP Addresses] section:
5.10 [M_SP_NA_1 104]
This section defines the monitored single-point database. This information is
sourced from the database and is transferred to the remote Client unit. Each
point indicates one of two states, 1 = Bit On, 0 = Bit Off.
This section takes the following parameters:
Point #
DB Address
Group(s)
IV DB Bit
Each point is one bit and the DB address value corresponds to the bit offset in
the module memory database. For additional information on how to set these
parameters, see the Reference chapter of this manual.
Page 92 of 201
ProSoft Technology, Inc.
March 4, 2013