ProSoft Technology PTQ-104S User Manual
Page 66

Module Configuration
48TPTQ-104S Rev 1 ♦ 47TQuantum Platform
12TUser Manual
46TIEC 60870-5-104 Server for Quantum
The following example shows how this could be accomplished.
5.4.2 Set Up Command Function 2 (Write data to the Quantum)
This section provides information on how to write data from the module to the
Quantum.
Command Function 2 (two) is designed to transfer data from the module to the
Quantum on a continuous basis. The command(s) required to transfer your
application data should be entered in the [BACKPLANE DATA EXCHANGE]
section of your configuration file as required.
This command takes the following parameters:
Command type: 2 (Write data to the Quantum)
PTQ Database Address: The source of the data within the PTQ to be sent to
the Quantum.
Point Type: The type of register within the Quantum (0:x = 0, 1:x = 1 3:x = 3
or 4:x = 4)
Quantum Address: The destination register within the Quantum. The address
is expressed without the use of the register range, for example 400001 would
be entered as 1 (400001 - 400000 = 1 or 40001 - 40000 = 1)
Word Count: The number of words to copy. The length of this copy may be
any length of 1 to 130 inclusive. If your application requires the movement of
additional data you may enter additional commands.
Page 66 of 201
ProSoft Technology, Inc.
March 4, 2013