Module Configuration
48TPTQ-104S Rev 1 ♦ 47TQuantum Platform
12TUser Manual
46TIEC 60870-5-104 Server for Quantum
Block Format for Read
Word Offset in Block
Data Field(s)
Description
0
Done Flag
The word will be set to 0 when the command is
complete.
1
Block ID
This word will contain the value of 9250
2
Scan Count
This status value contains a counter incremented
on each scan of the module's main loop.
3 to 4
Product Name
This two-word data area contains the text values
representing the product name.
5 to 6
Revision
This two-word data area contains the text values
for the revision number.
7 to 8
Op Sys #
This two-word data area contains the text values
for the operating system number.
9 to 10
Run Number
This two-word data area contains the text values
for the run number.
11
Number of block
reads
This data area contains the total number of block
read errors.
12
Number of block
writes
This word contains the total number of block write
errors.
13
Number of blocks
parsed
This word contains the total number of write
blocks successfully parsed.
14
Number of block
transfer errors
This word contains the total number of block
transfer errors.
15
t0 Timeout
Number of t0 errors recognized by the module
16
t1 Timeout
Number of t1 errors recognized by the module
17
t2 Timeout
Number of t2 errors recognized by the module
18
t3 Timeout
Number of t3 errors recognized by the module
19
Receive Sequence
This word contains the current Receive Sequence
number (NR) sent by the module. This value is a
part of every message sent to the client unit.
20
Bad Address
This word contains the number of messages
received with a wrong Common ASDU Address
value
21
Bad Length
This word contains the number of messages
received by the host that does not contain a valid
length field
22
Rx Count
Number of messages sent
23
Tx Count
Number of messages received
24
Socket State
This word contains the current socket state as
follows:
-1 = Open Socket
0 = Wait for Connection
1 = Transmit Message if Ready
2 = Receive Packet and process message
3 = Process multiple messages in packet
50 = Send TestFR ACT
51 = Wait for TestFR Con
60 = Send S-Format Message
1000 = Close Socket
1001 = Wait for Socket to Close
25
Socket Open Count
This word contains the number of times the socket
listen function was executed
Page 70 of 201