Station interrogation, Clock synchronization – ProSoft Technology PTQ-104S User Manual
Page 187

48TPTQ-104S Rev 1 ♦ 47TQuantum Platform
Reference
46TIEC 60870-5-104 Server for Quantum
12TUser Manual
Double transmission of information objects with cause of transmission
spontaneous
(Station-specific parameter, mark each information type "X" where both a Type
ID without time and corresponding Type ID with time are issued in response to a
single spontaneous change of a monitored object)
The following type identifications may be transmitted in succession caused by a
single status change of an information object. The particular Information Object
Addresses for which double transmission is enabled are defined in a project-
specific list.
Single-point information M_SP_NA_1, M_SP_TA_1, M_SP_TB_1 and
M_PS_NA_1
Double-point information M_DP_NA_1, MDP_TA_1 and M_DP_TB_1
Step position information M_ST_NA_1, M_ST_TA_1 and M_ST_TB_1
Bitstring of 32 bit M_BO_NA_1, M_BO_TA_1 and M_BO_TB_1
Measured value, normalized value M_ME_NA_1, M_ME_TA_1, M_ME_ND_1
and M_ME_TD_1
Measured value, scaled value M_ME_NB_1, M_ME_TB_1 and M_ME_TE_1
Measured value, short floating point number M_ME_NC_1, M_ME_TC_1 and
M_ME_TF_1
Station Interrogation
(Station-specific parameter, mark "X" if function is only used in the standard
direction, "R" if only used in the reverse direction, and "B" if used in both
directions)
global
group 1
group 7
group 13
group 2
group 8
group l4
group 3
group 9
group 15
group 4
group 10
group 16
group 5
group 11
group 6
group 12
Clock synchronization
(Station-specific parameter, mark "X" if function is only used in the standard
direction, "R" if only used in the reverse direction, and "B" if used in both
directions)
Clock synchronization
Day of week used
RES1, GEN (time tag substituted/not substituted) used
SU-bit (summertime) used (Optional)
ProSoft Technology, Inc.
Page 187 of 201
March 4, 2013