46TIEC 60870-5-104 Server for Quantum
12TUser Manual
5.6.11 Error Offset
0 to 3980
-1 to disable
This parameter sets the location in the module’s internal database when the
status and error information for the server will be stored. Enter a valid database
address of 0 to 3980 to store the information, or enter -1 to disable.
5.6.12 Command Delay Timer
1000 to 60000 milliseconds
This value is used for time-tag validity verification for the ASDUs listed
below. The received commands will only be accepted if [timestamp + Command
Delay Timer] is greater than the module's own time.
58: Single command with time tag CP56Time 2a
59: Double command with time tag CP56Time 2a
60: Regulating step command with time tag CP56Time 2a
61: SetPoint command, normalized value with time tag CP56Time 2a
62: SetPoint command, scaled value with time tag CP56Time 2a
63: SetPoint command, short floating point with time tag CP56Time 2a
107: Test command with time tag CP56Time2a
If the value is less than 1000 milliseconds, the module will default to 5000
milliseconds
5.6.13 Maximum ASDU Resp Len
25 to 246
This parameter limits the maximum size of the ASDU portion of a response
message. Most applications will use a value of 246.
5.6.14 Freeze Start Type
D
=
D
AY
,
H
=
H
OUR
,
M
=
M
INUTE
,
N
=
N
OT USED
The Freeze Start Type parameter defines when the module starts sending the
M_IT messages.
5.6.15 Interval for Freeze
0 to 65535
seconds
Freeze Start Type and Interval for Freeze are used if Mode A operation is to be
used for the counter freeze operation. If they are not used, the module will
operate in Mode D.