Information object address, Cause of transmission, Length of apdu – ProSoft Technology PTQ-104S User Manual
Page 181: 3 selection of standard asdus, Process information in monitor direction

48TPTQ-104S Rev 1 ♦ 47TQuantum Platform
Reference
46TIEC 60870-5-104 Server for Quantum
12TUser Manual
Information object address
(System-specific parameter)
One octet
Structured
Two octets
Unstructured
Three octets
Cause of transmission
(System-specific parameter)
One octet Two octets (with originator address)
Length of APDU
(System-specific parameter, specify the maximum length of the APDU per
system)
The Maximum length of the APDU is 246 (default). The maximum length may be
reduced by the system.
255 Maximum length of APDU per system
9.6.3 Selection of standard ASDUs
Process information in monitor direction
(Station-specific parameter; mark each Type ID "X" if it is only used in the
standard direction, "R" if only used in the reverse direction, and "B" if used in
both directions)
Type ID
Description
Type
<1>
Single-point information
M_SP_NA_1
<2>
Single-point information with time tag
M_SP_TA_1
<3>
Double-point information
M_DP_NA_1
<4>
Double-point information with time tag
M_DP_TA_1
<5>
Step position information
M_ST_NA_1
<6>
Step position information with time tag
M_ST_TA_1
<7>
Bitstring of 32 bit
M_BO_NA_1
<8>
Bitstring of 32 bit with time tag
M_BO_TA_1
<9>
Measured value, normalized value
M_ME_NA_1
<10>
Measured value, normalized value with
time tag
M_ME_TA_1
<11>
Measured value, scaled value
M_ME_NB_1
<12>
Measured value, scaled value with time
tag
M_ME_TB_1
<13>
Measured value, short floating point
value
M_ME_NC_I
<14>
Measured value, short floating point
value with time tag
M_ME_TC_1
<15>
Integrated totals
M_IT_NA_1
<16>
Integrated totals with time tag
M_IT_TA_1
<17>
Event of protection equipment with time
tag
M_EP_TA_1
<18>
Packed start events of protection
M_EP_TB_1
ProSoft Technology, Inc.
Page 181 of 201