ProSoft Technology PTQ-104S User Manual
Page 57

48TPTQ-104S Rev 1 ♦ 47TQuantum Platform
Module Configuration
46TIEC 60870-5-104 Server for Quantum
12TUser Manual
The first command states:
Field
Value
Meaning
Command Type
1
The type of operation to perform
1 = Read data from the Quantum into the PTQ
PTQ Address
0
The destination address within the PTQ
Point Type
4
The range of registers to read from the Quantum
4 = 4:x style register
Quantum Address
1
The starting address of the data within the Quantum
This would be Point Type + offset
Example: 40000 + 1 = 40001
Word Count
100
The number of registers to transfer
The second command states:
Field
Value
Meaning
Command Type
1
The type of operation to perform
1 = Read data from the Quantum into the PTQ
PTQ Address
100
The destination address within the PTQ
Point Type
4
The range of registers to read from the Quantum
4 = 4:x style register
Quantum Address
104
The starting address of the data within the Quantum
This would be Point Type + Quantum Address
Example: 40000 + 104 = 40104
Word Count
107
The number of registers to transfer
The following diagram shows the result of this example.
Quantum Memory Address
PTQ Memory Address
40001
0
40010
First Command
9
40020
19
40030
29
40040
39
…
40060
59
40070
69
40080
79
40090
89
40100
99
40104
100
40111
Second Command
110
…
40200
199
40207
206
…
…
ProSoft Technology, Inc.
Page 57 of 201