3 hardware specifications, 4 functional specifications – ProSoft Technology PTQ-104S User Manual
Page 129

48TPTQ-104S Rev 1 ♦ 47TQuantum Platform
Reference
46TIEC 60870-5-104 Server for Quantum
12TUser Manual
9.1.3 Hardware Specifications
Specification
Value
Backplane Current Load
1100 mA maximum @ 5 Vdc ± 5%
Operating Temperature
0°C to 60°C (32°F to 140°F)
Storage Temperature
-40°C to 85°C (-40°F to 185°F)
Relative Humidity
5% to 95% (without condensation)
Vibration
Sine vibration 4-100 Hz in each of the 3 orthogonal
axes
Shock
30G, 11 mSec. in each of the 3 orthogonal axes
Dimensions (HxWxD),
Approx.
250 x 40.34 x 103.85 mm
9.84 x 1.59 x 4.09 in
LED Indicators
Module Status
Backplane Transfer Status
Serial Port Activity LED
Serial Activity and Error LED Status
Debug/Configuration Port (Debug)
CFG Port (DEBUG)
DB-9M PC Compatible
RS-232 only
No hardware handshaking
Application Ports
Application Ethernet port RJ45 Connector
Link and Activity LED indicators
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60
s, applied as specified in section 5.3.2 of IEC 60950:
1991
Ethernet Broadcast Storm Resiliency = less than or
equal to 5000 [ARP] frames-per-second and less than
or equal to 5 minutes duration
9.1.4 Functional Specifications
The PTQ-104S module accepts data read/write commands from a master/client
on the network. In addition, the module can be configured to generate unsolicited
messages in either a spontaneous or cyclic fashion.
The module has 4000 words of user defined internal register space that are
accessible to the protocol driver and to the Quantum processor memory. Any of
the supported database types can be individually located (within the total
database size limit of 4000 words) and each database point is mapped within the
module and can be assigned to one or more Groups. The supported database
point types are:
Database Type
Description
Event Generation Point Size
M_SP_NA
Monitored single-point database
State Change
1 bit
M_DP_NA
Monitored dual-point database
State Change
2 bits
M_ST_NA
Monitored step-point database
State Change
1 byte
M_ME_NA
Monitored normalized-point database
Dead-band
1 word
M_ME_NB
Monitored scaled-point database
Dead-band
1 word
M_ME_NC
Monitored short-float point database
Deadband
2 words
M_IT_NA
Monitored integrated total database
N/A
2 words
C_SC_NA
Command single-point database
N/A
1 bit
ProSoft Technology, Inc.
Page 129 of 201