4 error status table, Error status table – ProSoft Technology PTQ-104S User Manual
Page 176

Reference
48TPTQ-104S Rev 1 ♦ 47TQuantum Platform
12TUser Manual
46TIEC 60870-5-104 Server for Quantum
9.4
Error Status Table
This section contains a listing of the PTQ-104S module's status data area, copied
automatically to the database starting at address 4000. To request the complete
status block, refer to Read Status (9250) on page 69.
Word Offset in Block
Data Field(s)
Description
4000
Scan Count
This status value contains a counter incremented
on each scan of the module's main loop.
4001 to 4002
Product Name
This two-word data area contains the text values
representing the product name.
4003 to 4004
Revision
This two-word data area contains the text values
for the revision number.
4005 to 4006
Op Sys #
This two-word data area contains the text values
for the operating system number.
4007 to 4008
Run Number
This two-word data area contains the text values
for the run number.
4009
Reserved
Reserved
4010
Block Reads
4011
Block Writes
4012
Blocks Parsed
4013
Block Errors
4020
Send Sequence
This word contains the current Send Sequence
number (NS) sent by the module. This value is a
part of every message sent to the client unit.
4021
Receive Sequence This word contains the current Receive Sequence
number (NR) sent by the module. This value is a
part of every message sent to the client unit.
4022
Ack Sequence
This value increments every time the messages
sent by the module are acknowledged. The client
acknowledges a number of APDUs when it returns
the Receive Sequence Number up to the number
whose APDUs are properly received. The module
will hold the APDUs in a buffer until it receives back
its own Send Sequence Number as a Receive
Sequence Number. The buffer status information is
available at the following status parameters: (In
Queue, Queue First, Queue Index)
4023
Received Packets
This word contains the number of messages
received by the client but without being
acknowledged by the module
4024
In Queue
This word contains the number of messages in the
queue that have not been acknowledged by the
client yet.
4025
Queue First
This word should contain a value of 0.
4026
Queue Index
This word contains the current index number of the
latest message in the buffer queue.
4027
Tx Count
Number of messages received
4028
Rx Count
Number of messages sent
4029
t0 Timeout
Number of t0 errors recognized by the module
4030
t1 Timeout
Number of t1 errors recognized by the module
4031
t2 Timeout
Number of t2 errors recognized by the module
4032
t3 Timeout
Number of t3 errors recognized by the module
Page 176 of 201