M_me_nc and m_it_na – ProSoft Technology PTQ-104S User Manual
Page 147

48TPTQ-104S Rev 1 ♦ 47TQuantum Platform
Reference
46TIEC 60870-5-104 Server for Quantum
12TUser Manual
Bit
15
14
13
12
11
10
9
8
7 6 5 4 3 2 1 0
6000h
0.75
0
1
1
0
0
0
0
0
0 0 0 0 0 0 0 0
3210h
0.395751953125
0
0
1
1
0
0
1
0
0 0 0 1 0 0 0 0
Examples:
A value of 4000hex (only Bit 14 set, all others clear) is interpreted as 0.5 decimal
A value of 2000hex (only Bit 13 set, all others clear) is interpreted as 0.25
decimal
A value of 1000hex (only Bit 12 set, all others clear) is interpreted as 0.125
decimal
... and so on until...
A value of 0001hex (Only Bit 0 set, all others clear) is interpreted as
0.000030517578125
Therefore, the actual data values transmitted may be any combination of the
decimal values for any given bit pattern.
M_ME_NC and M_IT_NA
The monitored measured short floating point and monitored integrated total
points occupy two words with double-word addressing.
For example, if you configured the following points:
The following table describes how these points would be stored in the module:
500
Words 40 and 41 (Double-word address 20)
501
Words 64 and 65 (Double-word address 32)
502
Word 104 and 105 (Double-word address 52)
ProSoft Technology, Inc.
Page 147 of 201