M_me_nc, Controlling the generation of events, General (all points) – ProSoft Technology PTQ-104S User Manual
Page 166

Reference
48TPTQ-104S Rev 1 ♦ 47TQuantum Platform
12TUser Manual
46TIEC 60870-5-104 Server for Quantum
M_ME_NC
Monitored Measured Normalized Point
Associated Parameter Point
600
2600
601
2601
602
2602
603
2603
...
...
609
2609
In order to send a change of deadband for M_ME_NC Point 600, the Client
would send a command type 110 to point 2600.
Controlling the Generation of Events
Some applications may require that only some points should generate events.
The application will receive current values from points which have not been
configured to generate events only by issuing a poll request, or what the protocol
specification calls an interrogation. Other applications may require that all
configured points generate events.
The PTQ-104S module offers much flexibility for event control. You may control
whether or not events will be generated at three (3) different levels:
1 At the General Application Level (all configured points of all types)
2 At the Data Type Level (all configured points of any data type)
3 At the Individual Point Level (any specific point of any data type)
General (All Points)
The user may control how frequently the module will scan the database for
events using the following configuration parameter:
Page 166 of 201
ProSoft Technology, Inc.
March 4, 2013