Iec-870-5-104] section: error offset – ProSoft Technology PTQ-104S User Manual
Page 178

Reference
48TPTQ-104S Rev 1 ♦ 47TQuantum Platform
12TUser Manual
46TIEC 60870-5-104 Server for Quantum
Word Offset in Block
Data Field(s)
Description
7 to 8
Run Number
This two-word data area contains the text values
for the run number.
9
Reserved
Reserved
[IEC-870-5-104] section: Error Offset
Word Offset in Block
Data Field(s)
Description
0
t0 Timeout
Number of t0 errors recognized by the module
1
t1 Timeout
Number of t1 errors recognized by the module
2
t2 Timeout
Number of t2 errors recognized by the module
3
t3 Timeout
Number of t3 errors recognized by the module
4
Sequence Number
Errors
This word contains the number of sequence
number errors recognized by the module. When the
send sequence number received by the module
does not match the expected sequence number,
the connection is closed and this counter is
incremented
5
Bad Address
This word contains the number of messages
received with a wrong Common ASDU Address
value
6
Bad Length
This word contains the number of messages
received by the host that does not contain a valid
length field
7
Active
1 = Yes, 0 = No.
8
Socket State
This word contains the current socket state as
follows:
-1 = Open Socket
0 = Wait for Connection
1 = Transmit Message if Ready
2 = Receive Packet and process message
3 = Process multiple messages in packet
50 = Send TestFR ACT
51 = Wait for TestFR Con
60 = Send S-Format Message
1000 = Close Socket
1001 = Wait for Socket to Close
9
Socket Open Count This word contains the number of times the socket
listen function was executed
10
Socket Close
Count
This word contains the number of times the an
active close function was executed
11
Socket Connect
Count
This word contains the number of times a
connection was established between with the
remote host unit
Page 178 of 201
ProSoft Technology, Inc.
March 4, 2013