Parameter in control direction, File transfer – ProSoft Technology PTQ-104S User Manual
Page 184

Reference
48TPTQ-104S Rev 1 ♦ 47TQuantum Platform
12TUser Manual
46TIEC 60870-5-104 Server for Quantum
Parameter in control direction
(Station-specific parameter, mark each Type ID 'X" if it is only used in the
standard direction, "R" if only used in the reverse direction, and "B" if used in
both directions)
Type ID
Description
Type
<110>
Parameter of measured value,
normalized value
P_ME_NA_1
<111>
Parameter of measured value, scaled
value
P_ME_NB_1
<112>
Parameter of measured value, short
floating point value
P_ME_NC_1
<113>
Parameter activation
P_AC_NA_1
File transfer
(Station-specific parameter, mark each Type ID "X" if it is only used in the
standard direction, "R" if only used in the reverse direction, and "B" if used in
both directions)
Type ID
Description
Type
<120>
File ready
F_FR_NA_1
<121>
Section ready
F_SR_NA_1
<122>
Call directory, select file, call file, call
section
F_SC_NA_1
<123>
Last section, last segment
F_LS_NA_1
<124>
Ack file, ack section
F_AF_NA_1
<125>
Segment
F_SG_NA_1
<126>
Directory
F_DR_TA_1
9.6.4 Type identifier and cause of transmission assignments
(Station-specific parameters)
Shaded boxes: option not required
Black boxes: option not permitted in this companion standard
Blank boxes: functions or ASDU not used
Mark Type Identification/Cause of Transmission combinations: 'X" if only used in
standard direction, "R" if only used in reverse direction, and "B" if used in both
directions.
Type Identification
Cause of transmission
1 2 3 4 5 6 7 8 9 10 11 12 13 20
to
36
37
to
41
44 45 46 47
<1>
M_SP_NA_1
X X X
X
X
<3>
M_DP_NA_1
X X X
X
X
<5>
M_ST_NA_1
X X X
X
X
Page 184 of 201