Contents

MVI69-GEC ♦ CompactLogix or MicroLogix Platform

User Manual

Page 22 of 86

ProSoft Technology, Inc.

February 18, 2014

2 Click the

[+]

sign next to any

icon to view module information and configuration

options.

3 Double-click any

icon to open an Edit

dialog box.

4 To edit a parameter, select the parameter in the left pane and make your changes in the

right pane.

5 Click OK

to save your changes.

Printing a Configuration File

1 In the main PCB window, right-click the M

ODULE

icon and choose V

IEW

C

ONFIGURATION

.

2 In the View Configuration dialog box, open the F

ILE

menu, and choose P

RINT

.

3 In the Print dialog box, choose the printer to use from the drop-down list, select the

printing options, and then click OK.

2.2

[Module]

This section of the file describes the database setup and module level parameters.

[Module]
Module Name: MVI69-GEC Communication Module DEFAULT

0 to 80

characters

Specifies a name to identify the module and the configuration file.

2.3

[Server x]

You can configure up to five servers ([Server 0] through [Server 4]). The configuration
section for each server contains the same set of parameters. You can configure the
parameters for each server to meet the requirements of your application.

2.3.1 Enabled

Yes or No

This parameter determines if the server will be utilized by the module. If a value of "Yes" is
entered, the server will be used. Any other value will disable the server.

2.3.2 Service Port Number

1 to 65535

This parameter sets the TCP/IP service port for this server. Each server can have its own
unique service port or can share the same number with other servers.

2.3.3 Connection Timeout

0 or 5000 to 65535

This parameter specifies the number of milliseconds the server will permit the server to be
inactive after a connection is made before closing the socket. This timeout period is reset on