Figure 53 typical operation modes, Typical operation modes, On. figure 53 illustrates the v – Emerson Series 600T User Manual

Page 62: System overview 50

background image

System Overview

50

Figure 53 Typical operation modes

KEY #

MODE

DESCRIPTION

1

READY

Idle condition waiting for event

2

DISCHARGE

3

CHARGE

FS supporting the critical load

Charging to top speed

A

B

C

D

E

Grid Supply lost ,FS supporting the load

Generator Starts , A.T.S. transfers the load

FS fully charged ready to support the load

FS supports the load as the A .T.S. transitions back to grid supply

FS fully charged ready to support the load

DC Bus Voltage

A

B

C

D

E

DC

VOLTAGE

AC

VOLTAGE

R.P.M.

FS Speed

ZERO

SPEED

MIN

SPEED

TOP

SPEED

FS

MODES

1

2

3

1

2

1

3

V Float

Vcharge

Vreg

0 VAC

480

VAC

V Generator
V Grid
V Load

GEN

AC Power Flow

AC Power Flow

DC Power Flow

Flywheel
Module

ATS

Grid

UPS Module