background image

Installation

28

4.2.2 DC Power Connections

The instructions for installation of DC power connections vary according to the type of UPS intercon-

nection kit integrated into your Liebert FS unit. Follow the installation instructions in Appendix

A.0 - UPS Interconnection Kits for the relevant UPS interconnection kit installed in your unit.

4.2.3 Status/Control Connections

The instructions for installing Status/Control connections vary according to the type of UPS intercon-

nection kit that is integrated into your Liebert FS. Follow the installation instructions in Appendix

A.0 - UPS Interconnection Kits for the relevant UPS interconnection kit installed in your unit.

4.2.4 Ground Connections

A ground connection is available on the Liebert FS (see Figure 29). The electrical contractor must

ensure that the Liebert FS is effectively grounded to UPS chassis or UPS ground terminal. The

ground connection must be as short as possible. The maximum ground wire size is 1/0 AWG - 600VDC

wire (54mm

2

wire section). Wire size and installation must comply with all applicable local, regional

and national regulations (e.g., National Electric Code for USA). Check all connections with Multi-

meter to verify ground continuity. (Refer also to Appendix E.1 - Ground Test Procedure.

Figure 29 Ground connection on the Liebert FS

The tightening torque for the ground connections must be in accordance with Table 3. Use these val-

ues unless the equipment is labeled with a different torque value.

!

CAUTION

Ensure that all grounds are secure and free of corrosion. Proper grounding is necessary for

optimum performance, safety and reliability.

Table 3

Tightening torque for ground connection

Ground Wire Gauge

Tightening Torque

AWG

Approximate metric

equivalent wire section (mm

2

)

Inch-

pounds

N-m

4

21

110 12

2

34

150 17

1

42

150 17

1/0

54

180

20

Ground Terminal

Locations (DC

ground and filter

caps if required)

Side panel

removed for

clarity.