Appendix F.1 Overview

The Liebert FS must be operated with a backup AC power supply to protect the unit’s mechanical

bearings if:

• the external DC supply is lost and
• the Liebert FS has developed a fault

If these two events occur simultaneously, the backup power supply will power the magnetic levitation

hardware to prevent the rotating group from running on the mechanical touchdown bearings.
This section details the function of the backup power supply and how it should be attached to the

Liebert FS. This is supplementary information—refer to appropriate sections of the user manual for

details on installation and operation.

Appendix F.2 Backup AC Power Supply Specification

Note: Connection to a 480VAC supply requires a 480 to 110 transformer, available from Liebert as an

option.

Appendix F.3 Recommended Backup Power Supply Configuration

Voltage:

110 to 230VAC, 400VA

Frequency: 50 to 60Hz

If the Liebert FS

is operating:

Liebert recommends:

For details, see:

In parallel

with batteries

Attaching the backup AC power supply to the output of the UPS.

Figures 156 and 157

Without batteries

Feeding the backup AC supply from a separate, protected supply.

This may be the output of another UPS or a supply from a separate

feeder circuit.

Figures 158 and 159