Auxiliary Backup AC Power Supply

152

Appendix F.3.2

Operating the Liebert FS Without Batteries

If the Liebert FS is operating without batteries, Liebert recommends feeding the backup AC power

supply from a separate, protected supply. This may be the output of another UPS or a supply from a

separate feeder circuit (see Figures 158 and 159).

Figure 158 A single Liebert FS unit operating with a UPS and without batteries attached to the DC bus

Figure 159 Multiple Liebert FS units operating with a UPS and without batteries attached to the DC bus

BACKUP AC

POWER SUPPLY

Liebert FS

Grid

Supply

UPS

Output

UPS

DC Bus

Fed from a protected AC

supply, either the output

of another UPS or a

separate feeder supply

3 Liebert FS Units

Grid

Supply

UPS

Output

UPS

DC Bus

BACKUP AC

POWER

SUPPLY

Distribution

panel*

Fed from a protected AC

supply, either the output

of another UPS or a

separate feeder supply

* NOTE:

Distribution panel allows

removal of a Liebert FS without

disrupting the other units