Maintenance

76

7.6

Optional Air Filters

The optional air filters must be inspected and serviced on a regular schedule. The period between

inspections will depend upon environmental conditions. Under normal conditions, the air filters will

require cleaning or replacement approximately every 12 months.

Abnormal or dusty conditions will require more-frequent cleaning and replacement of air filters

(sometimes as often as every two months). Inspect installations in new buildings more often, then

extend the inspection period as experience dictates.

7.7

Torque Requirements

All electrical connections must be tight. Table 12 provides the torque values for the connections in

the Liebert FS. Use these values unless the equipment is labeled otherwise.

7.8

Detecting Trouble

It is important that the operator check the instrument readings if abnormal equipment performance

is suspected. Any metered value that differs appreciably from normal could mean an impending mal-

function and should be investigated.
Items to check include:

• Alarm messages indicate malfunction or impending malfunction. A daily check of the operator

control panel will help to provide an early detection of problems. Refer to Table 16 to interpret

alarm messages.

• Tracing a problem to a particular section is facilitated by alarm messages and the metered

parameter indications. These are stored in the Status Reports and can be displayed at the opera-

tor control panel or at an optional terminal. A Liebert Global Services engineer will be familiar

with test points inside the unit.

!

CAUTION

Be certain recyclable filter elements are dry before reinstalling them in the Liebert FS.

Table 12

Torque specifications (unless otherwise labeled)

Nut And Bolt Combinations

Bolt Shaft Size

Grade 2

Standard

Electrical Connections

With Belleville Washers

Lb-in

N-m

Lb-in

N-m

1/4

53

6.0

46

5.2

5/16

107

12

60

6.8

3/8

192

22

95

11

1/2

428

48

256

29

Circuit Breakers with Compression Lugs (For Power Wiring)

Current Rating

Lb-in

N-m

250A

250

28

Circuit Breakers with Compression Lugs (For Control Wiring)

AWG Wire Size or Range

Lb-in

N-m

#22 - #14

3.5 to 5.3

0.4 to 0.6