Operation

55

6.2.2 System MODE Indicators

The Liebert FS has nine modes of operation: OFF, STARTUP, CHARGE, READY, DISCHARGE,

SHUTDOWN, COAST, FAULT and STANDBY. These are displayed on the main screen of the control

panel as identified in Figure 55. Table 5 lists the system Modes along with the corresponding Con-

tactor Status, and the Conditions required to operate in these Modes: external voltage range, speed

and command.

6.2.3 System STATUS Indicators

The Liebert FS system displays multiple status conditions during operation. Table 6 shows the com-

plete list of status indicators for the Liebert FS and the corresponding condition.

NOTE:
See 5.3 - Modes of Operation for further details on modes of operation.

Table 5

Operation modes

Mode

Contactor

Condition

External Voltage

Speed

Command

OFF

Open

Vext < Vchg

0 ~ 3500

STANDBY

Open

Vext > Vchg

0 ~ 200

STARTUP

Close

Vext > Vchg

200 ~ Min Speed

STARTUP

CHARGE

Close

Vext > Vchg

Min Speed ~ Max Speed

STARTUP

READY

Close

Vext > Vchg

Max Speed ~ Max Speed + 200

STARTUP

DISCHARGE

Close

Vext < Vchg

Min Speed ~ Max Speed

STARTUP

COAST

Close

330 < Vext < Vchg

200 ~ Min Speed

STARTUP

SHUTDOWN

Open

Vext < 330

200 ~ Min Speed

STARTUP

Open

Any

Min Speed ~ Max Speed

SHUTDOWN

Close

Vext > 330

200 ~ Min Speed

SHUTDOWN

FAULT

Open

Any

0 ~ Max Speed

STANDBY

After CLRFLT

Min Speed: Minimum operating speed; State of Charge (SOC) will be 0% at this speed.
Max Speed: Maximum operating speed; State of Charge (SOC) will be 100% at this speed.

Table 6

System status indicators

Message

Condition

1

OK

All systems operating normally.

2

READY

All systems operational and ready for startup.

3

APPLY 520*V

External voltage is less than the Charge Voltage*

4

n WARNINGS

Multiple warnings

5

n FAULTS

Multiple faults

6

OVERSPEED

Speed is higher than the Max Speed plus 200 RPM

7

TESTING VACUUM

Vacuum testing at 10000 RPM

8

OPENING CONTACTOR

Waiting until the current is stabilized

9

CLOSING CONTACTOR

Waiting until the voltages are stabilized

10

WAIT

Waiting until the voltages are stabilized

* Charge voltage is an adjustable user parameter; 520V is used only as an example.