Appendix A.3.2 Status/Control Connections - Liebert Npower UPS Interconnection Kit

The status/control interface is the Liebert Npower Battery Information Board (BIB). The connection

of the BIB is described in Figure 140 - Control wiring diagram—Liebert FS - optional electri-

cally operated circuit breaker Liebert Npower units. Refer to this drawing to ensure that the

proper connections are performed. In case multiple Liebert FS units are connected to the same UPS

DC bus, refer to Figure 132 - Control wiring diagram, Liebert FS power rack system in paral-

lel for capacity to perform the Status/Control connections between each Liebert FS.
This interconnection kit includes Status/Control Connections that enable transfer of signals between

the Liebert FS system(s) and the UPS system such as:

• Circuit breaker status (closed/open); and
• Undervoltage relay coil excitation voltage.

The recommended gauge for status/control connection wires is 16 AWG - 600VDC (1.3mm

2

wire sec-

tion). Wire size and installation must comply with all applicable local, regional and national regula-

tions (e.g., National Electric Code for USA).

Appendix A.3.3 UPS Configuration - Liebert FS and Liebert Npower

To optimize the integration between the Liebert Npower UPS system and the Liebert FS, some

parameters must be checked on the UPS system:

• The UPS rectifier walk-in time must be set at a value as low as possible. Contact your Liebert rep-

resentative if your unit has received the upgraded board that permits the setting of “rectifier

walk-in time” lower than standard.

• Ensure that the “auto battery self test” has either been disabled or upgraded to accommodate

Liebert FS integration.

Appendix A.3.4 Liebert FS Configuration - Single Liebert FS Unit

The following Software Control Parameters must be set when the Liebert FS is connected to the

DC bus of the Liebert Npower UPS system.

NOTE
The Software Control Parameter values specified below are recommended. These values may

require adjustments due to the battery type. These must be used unless otherwise specified by

the Liebert-certified service technician at initial system startup. Instructions to set these

parameters on the Liebert FS are in 6.5.3 - Control Parameters Setup at Initial System

Startup.

Table 23

Liebert FS Software Control Parameters

Liebert FS Software

Control Parameter

Setting

Charge Voltage

520VDC

Regulation Voltage

510VDC

Vreg Delta

0VDC

Maximum Charge Current

See Table 24

Charge Amps/Volts

See Table 24

Table 24

Liebert FS Software Control Parameters varying with UPS size

UPS Output Rating (kVA)

30

40

50

65

80

100

130

Liebert FS Maximum Charge Current (A)

11

15

19

25

31

38

50

Liebert FS Charge Amps/Volts (A/V)

0.8

1.0

1.3

1.7

2.1

2.6

3.4