Unloading and Unpacking

14

3.2.1 Handling

The Liebert FS shipping package is designed to be handled using a forklift. Forklift operators must

avoid rough handling when picking up, moving and lowering it.

3.2.2 Unpacking

To reduce the possibility of shipping damage, flywheel cabinets are secured to the pallet by two

mounting brackets and two banding straps. These same two mounting brackets are used to mount the

cabinet to the floor.
Packing elements should be removed in this order to ease unpacking:
1. Cut and remove the banding straps (see Figure 8).

2. Remove hex head bolts holding mounting brackets to pallet as shown in Figure 9.
3. Remove lag bolts holding metal mounting brackets to pallet.
4. Remove mounting brackets from Liebert FS.

Figure 9

Removing lag bolts

!

CAUTION

Exhibit care when handling Liebert FS cabinet to avoid equipment damage or injury to

personnel. Failure to do so could throw off the calibration of the mechanical components

contained in the unit and possibly cause permanent damage.

!

CAUTION

The Liebert FS has sensitive electronics and mechanical components that have been

calibrated prior to shipment.

!

CAUTION

Test lift and balance the cabinet before transporting it. Maintain minimum tilt from vertical

at all times—do not exceed 15 degrees of tilt.

!

CAUTION

Sheet metal components and framework may have sharp edges.

!

CAUTION

Use care when removing banding straps and metal mounting brackets. The banding straps

are under tension and may snap violently, causing injury. Always wear proper eye and foot

protection when unpacking or installing the system.

Lag bolts

securing

Liebert FS to

shipping pallet

Metal mounting

bracket bolted to

shipping pallet