UPS Interconnection Kits

96

Appendix A.5 Installing the Liebert FS With a Liebert HiPulse UPS

The Liebert HiPulse UPS interconnection kit for the Liebert FS is compatible with the Liebert

HiPulse™ models in Table 28.

Appendix A.5.1 Description—HiPulse UPS Interconnection Kit

HiPulse UPS interconnection kit is composed of:
DC Power Interface

One Thermal-Magnetic Molded Case circuit-breaker rated for 250 ADC, 600VDC equipped with

auxiliary contacts: two (2) sets of Normally Open (NO) and Normally Closed (NC).

Status/Control Interface

One Status/Control Terminal Block used to ensure the status/control connections between the

Liebert FS and the Liebert HiPulse.

Appendix A.5.2 Status/Control Connections—Liebert HiPulse UPS Interconnection Kit

The status/control interface of the IKIT-A05 is the Status/Control Terminal Block. The connection of

the Status/Control Terminal Block is illustrated in Figure 102. Please refer to this drawing to ensure

that the proper connections are made. In case multiple Liebert FS units are connected to the same

UPS DC bus, please refer to Figure 144 to perform the Status/Control connections between each

Liebert FS.
This IKIT includes Status/Control Connections that enable transfer of “IKIT circuit-breaker status

(closed/open)” signals between the Liebert FS system(s) and the UPS system.

Figure 102 Liebert HiPulse status/control terminal block wiring

The recommended gauge for Status/Control Connection wires is 16 AWG – 600 VDC (approximate

metric equivalent: 1.3 mm² wire section). All wiring must comply with all applicable local, regional,

national regulations.

Table 28

Liebert HiPulse model ratings

UPS Output Rating

kVA

80

120

160

200

300

400

500

600

800

kW

64

96

128

160

240

320

400

480

640

4

2

3

5

7

8

9

6

1

10

Two rows

B

l

u

e

B

l

u

e

Y

e

l

l

o

w

Y

e

l

l

o

w

Yellow/

Blue

Yellow/

Blue

Row for

installation of

contractor wire

connections

This manual is related to the following products: