Appendix a.5.5 single liebert fs on ups dc bus, Appendix a.5.5, Single liebert fs on ups dc bus – Emerson Series 600T User Manual
Page 110: Appendix a.5.6, Table 29, Liebert fs software control parameter settings, Table 30, Table 31, Table 32
UPS Interconnection Kits
98
Appendix A.5.5 Single Liebert FS on UPS DC Bus
The following Liebert FS Software Control Parameters must be set when a single Liebert FS is con-
nected alone on the DC bus of the Liebert HiPulse UPS system.
Instructions on setting these parameters on the Liebert FS are found in 6.5.3 - Control Parameters
Setup at Initial System Startup.
Appendix A.5.6 Single Liebert FS in Parallel with Battery Pack on UPS DC Bus
The following Software Control Parameters must be reset when the Liebert FS is connected in paral-
lel with a battery pack on the DC bus of the Liebert Hipulse UPS system.
Instructions on setting these parameters on the Liebert FS are found in 6.5.3 - Control Parameters
Setup at Initial System Startup.
NOTE
The Software Control Parameter values specified below must be used unless otherwise
specified by the Liebert-certified service technician at Initial System Startup.
Table 29
Liebert FS Software Control Parameter settings
Liebert FS Software Control Parameter
Setting
Charge Voltage
436 VDC
Regulation Voltage
426 VDC
Vreg Delta
0 VDC
Maximum Charge Current
See Table 30
Charge Amps/Volts
See Table 30
Table 30
Liebert FS Software Control Parameters varying with UPS size
UPS Output Rating (kVA)
80
120
Liebert FS
Maximum Charge Current (A)
39
50
Liebert FS
Charge Amps/Volts (A/V)
4
5
NOTE
The Software Control Parameter values specified below must be used unless otherwise
specified by the Liebert-certified service technician at Initial System Startup. These values may
require adjustments due to the battery type.
Table 31
Liebert FS Software Control Parameter settings
Liebert FS Software Control Parameter
Setting
Charge Voltage
436 VDC
Regulation Voltage
426 VDC
Vreg Delta
0 VDC
Maximum Charge Current
See Table 32
Charge Amps/Volts
See Table 32
Table 32
Liebert FS Software Control Parameters varying with UPS size
UPS Output Rating (kVA)
80
120
Liebert FS Maximum Charge Current (A)
39
50
Liebert FS Charge Amps/Volts (A/V)
4
5