UPS Interconnection Kits

99

Appendix A.5.7 Liebert FS Configuration – Multiple Liebert FS Units

Liebert FS Software Control Parameters must be reset when multiple Liebert FS units are connected

in parallel on the DC bus of a Liebert HiPulse™ UPS system.
Instructions to set these parameters on the Liebert FS are found in 6.5.3 - Control Parameters

Setup at Initial System Startup.

Multiple Liebert FS Parallel Operation—Regular Configuration

Liebert FS Software Control Parameters must be reset when multiple Liebert FS units are connected

in parallel on the DC bus of a Liebert HiPulse™ UPS system for proper operation with longer run

times or higher backup power requirements. The Liebert FS units will contribute all together at the

same time to the task of supporting the UPS DC bus.
Instructions on setting these parameters on the Liebert FS are found in 6.5.3 - Control Parameters

Setup at Initial System Startup.

NOTE
In this configuration, the UPS DC bus usually does NOT have batteries in parallel with the

Liebert FS units, however, parallel operation with batteries is acceptable. If batteries to be used

are in parallel with the Liebert FS units on the UPS DC bus, contact your local Liebert sales

representative to arrange a review of the application.

NOTE
Your Liebert-certified service technician will configure the Software Control Parameter values

at Initial System Startup depending on the number of paralleled units.