Shutdown/Disassembly
11.1 Shutdown
DANGER
Lethal voltages are present in the AC terminals and cables!
Severe injuries or death may occur if the cables and terminals in the device are touched.
›
Complete disconnection only via the shutdown of the bulk power supply in front of the bidirec-
tional battery inverter.
Shutdown sequence
1. Shut down the device by pressing the "ON" button.
2. Open the DC main switch and isolate the DC lines.
3. Disconnect the battery voltage and precharge line.
4. Disconnect AC lines on the input (AC source) and output (AC load).
11.2 Disconnection
↻ Switch off the device.
↻ After shutdown, wait at least 30 minutes before working on the device.
5. Open the connection area.
6. Release the DC and AC cables from the connection terminals.
7. Pull out the cables.
»
Device has been disconnected. Continue with the disassembly.
11.3 Disassembly
↻ Switch off the device.
↻ Device disconnected.
1. Remove the device fastening.
2. Securely pack up the device if it is to be used later, or have the device disposed of in the correct manner.