1 connecting grounding, 2 connecting the battery – KACO blueplanet gridsave eco 5.0 TR1 User Manual
Page 23

Installation
Operating instructions for blueplanet-gridsave eco_EN
Page 23
Authorised electrician
7.2.1 Connecting grounding
The bidirectional battery inverter must be grounded to the earth system of the installation.
The cross-section of the copper wire must be at least the same cross-section of the connected outer conductor, and
at least 6 mm².
Please refer to local regulations for more information on the size of the ground cable.
Ground the device by connecting the protective earth conductor from a suitable location (e.g. main earthing bar) to
the ground terminal of the device. The bidirectional battery inverter is suitable for earthing systems.
7.2.2 Connecting the battery
Shunt1 A
Shunt1 B
Temp
gridsave eco
Battery
S+
Mid
S-
B+
B-
Main battery
isolator
Battery measurement /
precharge isolator
*
*
Figure 12: Battery connection diagram
* Connect S+ and S- cables to the battery poles for voltage measurement.
NOTE
The wiring diagrams do not show the overcurrent protective devices!
Both the main battery cables and for battery measurement / precharging, an overcurrent protective
device is recommended that is able to act as an isolator switch to shut down the device in the event
of a fault or for maintenance purposes (available as additional accessories).
NOTE
The DC cables must be permanently connected and no plug-and-socket connections are permitted!
›
Disconnecting the cable during operation may cause arcing which can cause equipment damage
or injuries.
›
When disconnecting the cables, always first ensure that device is shut down, cables B+ and B- are
disconnected, followed by the sense/precharge cables. Connections are made in the reverse order.