1 display of status and fault messages – KACO blueplanet gridsave eco 5.0 TR1 User Manual
Page 29

Configuration and Operation
Operating instructions for blueplanet-gridsave eco_EN
Page 29
8.1.1 Display of status and fault messages
Item Meaning
LED
Status
Description
1
Generator
status
Status LED displays generator operation:
•
No generator control
•
Generator starting
•
Generator running
•
Generator cannot start automatically
•
Generator fault
Off
Green flash-
ing green
Yellow flash-
ing
Red flashing
2
AC source
Blue
Input of external alternating voltage from
•
generator or
•
power grid
3
Transfer
Off
Blue
Alternating voltage outside tolerance range for synchronisation
External alternating voltage connected to AC load output.
(The status LED flickering is normal)
4
Consumer (AC
load)
Blue
Consumers are supplied with AC voltage. (Display also possible
without DC connection on the device)
5
Power mode
Status LED displays device operation:
•
Device in no-load operation. Monitoring and data acquisition
active
•
Device is active in save mode and measures the load condi-
tions
Green
Slow flashing
in green
Fast flashing
in green
•
Device is preparing to start.
Green
Red flashing
•
Device is switched on
•
Interrupted power circuit or poor battery connection > no out-
put of inverter power possible
Red
•
Fault detected
6
Export
Green
Energy is exported to the grid with on-grid plant
Flashing in
green
•
AC load is supplied
7
Battery status
Display of the battery voltage (standard) or charge status.
With active SoC control, the proportion of usable residual charge
in the batteries is displayed. The usable charge is between 100 %
SoC and the shutdown SoC.
upper
range
Green
Display of the trickle voltage or higher voltage
Red
•
Immediate shutdown due to high DC voltage
lower
range
Yellow
•
Battery weak
Red flashing
•
Immediate shutdown due to low DC voltage
Red
•
Shutdown due to weak battery
Show all
Red flashing
•
Shutdown if low battery voltage is removed !
In the case of an emergency, the operation of the device can
be maintained at reduced power via the battery shutdown
limit through to complete discharge.
This emergency function may damage the battery and the