beautypg.com

KACO XP83U-H6 (Canada) User Manual

Page 67

background image

Page 67

F15

MC21 Failure

Inverter AC side contactor
failure

Problem
• MC21 contactor is open
• Auxiliary switch is inoperable

Solution(s)
• Check the wiring connection
• Change the MC21

F16

Inv. Phase Order

Phase order failure on the
inverter side

Problem
• Phase order failure on the inverter
• Wrong phase rotation

Solution(s)
• Check the wiring connection

• Reverse two phases

F18

Inductor or TR
Over Temp

Inductor or transformer
temperature is above 150°C.

Problem
• Cabinet fan failure

Solution(s)
• Cleaning the filters
• Change the cabinet Fan

F20

PEBB 1 IGBT
Fault

PEBB IGBT U failure

Problem
• Short circuit in the IGBT

Solution(s)
• Visual inspection
• Change the PEBB

F21

PEBB 2 IGBT
Fault

PEBB IGBT V failure

F22

PEBB 3 IGBT
Fault

PEBB IGBT W failure

F24

PEBB Over
Temp. Analog

The temperature of the heat-
sink exceeds operational
parameters

Problem
• PEBB fan failure

Solution(s)
• Clean the filters
• Inspect and if necessary clean the heat-sink fins
• Change the PEBB Fan

F25

PEBB Over
Temp. Digital

The heat-sink over
temperature
generated by the thermal trip
device

Problem
• PEBB Fan Failure

Solution(s)
• Inspect and if necessary clean the heat-sink fins

Change the PEBB Fan

F30

Grid Over Voltage

Over voltage on the grid side

Problem
• The grid voltage is too high

Solution(s)
• Check the grid voltage
• Check the grid parameter

F31

Grid Under
Voltage

Under voltage on the grid side

Problem
• The grid voltage is too low

Solution(s)
• Check the grid voltage
• Check the grid parameter
• Check the MCB24

F30

Grid Over Voltage

Over voltage on the grid side

Problem
• The grid voltage is too high

Solution(s)
• Check the grid voltage
• Check the grid parameter

F31

Grid Under
Voltage

Under voltage on the grid side

Problem
• The grid voltage is too low

Solution(s)
• Check the grid voltage
• Check the grid parameter
• Check the MCB24

F32

Grid Over
Frequency

Over frequency on the grid
side

Problem
• The grid frequency is outside the permitted rang

Solution(s)
• Check the grid frequency