9. COMMISSIONING
DANGER!
Electric shock is possible from improper startup of the Inverter.
Death may result from burns and electric shock.
l
All procedures described in this section may only be conducted by qualified personnel.
If problems occur when performing the work described here, contact the technical support dept. at
KACO new energy Inc. +1 (415) 931-2046.
Visual Inspection
Inspect all large power cables and bus connections throughout the inverter to verify that they are tight.
Verify that all PV wires are connected with the proper polarity and tightened to the proper torque
specification.
Check the AC connections for proper phase rotation and that they are tightened to the proper torque
specification.
Verify that the AC and DC ground wires are connected correctly and tightened to the proper torque
specification.
Inspect the interior of the Inverter to insure that it is clear of tools, foreign objects, water, debris or documents.