Time intervals for maintenance work

Maintenance work

maintenance interval

(recommended)

Cleaning or replacing of the filter mats in the air intake

6 months *

Clean the heat sink-power section

12 months *

Inspection of a cabinet for strong dust sedimentation, pollution, moisture
and water penetration from the outside.

12 months

Inspection of all warning labels, replace if necessary.

12 month

Function test of the fans

12 month

Visual inspection of fuses, breakers and surge protection

12 month

Visual inspection of redundant auxiliary power supplies

12 month

Function test of the door contacts

12 month

Inspection of the run and fault indicators

12 month

* If the installation site is especially dirty, maintenance intervals will be reduced.