15. ERROR CODES
The Inverter can detect faults during operation. The inverter will display the fault in the GUI. Faults are
indicated in the GUI with an error code, and a plain text message with the error code and system plant name
in the text line will be sent to the system operator (only available if purchased and configured during setup).
This section describes how to recognize the types of faults and how to correct these faults.
Warnings
Code
Message
Warning description
Possible causes/Diagnosis
W01
SP1(PV SP) Failure
Failure of the PV side surge protector
(SP1)
Problem
• Lightning strike on or near the PV
system wiring
Solution(s)
• Visual inspection
• Change the SPD
W03
PV Fuse Failure
PV side Fuse failure(option)
Problem
• PV system wiring short
• Short circuit in the IGBT
Solution(s)
• Check the input current
• Check module wiring
• Change the FUSE
W20
PEBB Over Temp.
Warning
The temperature of the heat-sink of
the PEBB exceeds 75°C (167°F)
Problem
• PEBB Fan Failure
Solution(s)
• Clean the filters or PEBB heat-sink fins
• Change the PEBB Fan
W21
PEBB Fan Failure
PEBB
heat-sink fan failure
Problem
• PEBB Fan Failure
Solution(s)
• Change the PEBB Fan
W30
SP2(Grid SP) Failure
Failure of the grid side surge
protector (SP2)
Problem
• Lightning strike on or near the grid
system wiring
Solution(s)
• Visual inspection
• Change the SPD
W40
Test Mode
The system is working in test mode
Problem
• The system is working in test mode
Solution(s)
• Change the parameters in the GUI
W50
Cabinet Over
Temp. Warning
The temperature of the cabinet
exceeds operational parameters
Problem
• Cabinet Fan Failure
Solution(s)
• Clean the air filters
• Change the cabinet fan
W51
Cabinet Under
Temp. Warning
The temperature of the cabinet falls
below operational parameters
Problem
• Ambient temperature is too low for
operation
W52
Control SMPS
Failure
Failure of the control SMPS
Possible causes
• Failure of the control SMPS
Solution(s)
• Change the control SMPS