KACO XP83U-H6 (Canada) User Manual
Page 66

Page 66
Fault
Code
Message
Warning Description
Possible problem and solution(s)
F01
PV Over Voltage
PV voltage exceeds the
parameter
Problem
• The voltage of the solar generator is too high
Solution(s)
• Check the input voltage
• Check module wiring and system
F02
PV Over Current
PV current exceeds the
parameter
Problem
• The current of the solar generator is too high
• PV system wiring short
Solution(s)
• Check the input current
• Check module wiring and system
F04
CB10 (PV CB)
Trip
PV side circuit breaker(CB10)
tripped
Problem
• CB10 disconnect switch is open
• Auxiliary switch is inoperable, K10 contactor
failed closed
Solution(s)
• Check the wiring connection
• Change the CB10, replace K10 contactor
F05
PV Polarity
Failure
Polarity (+, -) of PV side is
reversed
Problem
• Polarity of PV side is reversed
Solution(s)
• Check the wiring connection and change if
necessary
F06
Ground Fault
PV side ground fault
Problem
• DC & ground are shorted causing the GFDI fuse
to open
Solution(s)
• Check the solar generator for a ground fault and
Replace the GFDI Fuse
F10
Inv. Over Voltage
Over voltage on the inverter
side
Problem
• The inverter voltage is too high
Solution(s)
• Check the inverter voltage
• Check the inverter parameter
F11
Inv. Under
Voltage
Under voltage on the inverter
side
Problem
• The inverter voltage is too low
Solution(s)
• Check the inverter voltage
• Check the inverter parameter
• Check the MC21
F12
Inv. Over
Frequency
Over frequency on the inverter
side
Problem
• The grid frequency is outside the permitted
range
Solution(s)
• Check the grid frequency
F13
Inv. Under
Frequency
Under frequency on the
inverter side
Problem
• The grid frequency is outside the permitted
range
Solution(s)
• Check the grid frequency
F14
Inv. Over Current
Over current on the inverter
side
Problem
• Short circuit in the IGBT
• Short circuit in the Grid
Solution(s)
• Check the grid connection
• Check the inverter connection